New 2014 Polyisocyanurate “R” Values

Discover changes in LTTR values for polyisocyanurate insulation from 2014, including varying "R" values per inch and impacts on insulation thickness requirements.

On January 1st, 2014, the Long-Term Thermal Resistance values (LTTR ) or “R” value for polyisocyanurate insulation will be reduced from 6 per inch to 5.6 per inch. To make things more confusing, the “R” value per inch is not consistent. The thicker the insulation, the greater the “R” value per inch. So, 1” polyisocyanurate insulation will have an “R” value of 5.6, where an identical 1.5” sheet will have an “R” value of 5.7 per inch. The following is a table comparing the old “R” values to the new “R” values:

One layer of rigid insulation

Thickness

Prior to 2014 “R” Values After 2014 “R” Values
LTTR Value “R” per inch LTTR Value “R” per inch
1” 6.0 6.0 5.6 5.7
1.5” 9.0 6.0 8.6 5.7
2” 12.1 6.1 11.4 5.8
3” 18.5 6.2 17.4 5.8
4” 25.0 6.2 23.6 5.9

Two Layers of rigid insulation

“R” Value Prior to 2014 Thickness After 2014 Thickness
15 2 layers of: 1.3” 2 layers of: 1.4”
20 2 layers of: 1.7” 2 layers of: 1.8”
25 2 layers of: 2.1” 2 layers of: 2.2”
30 2 layers of: 2.5” 2 layers of: 2.6”
35 2 layers of: 2.9” 2 layers of: 3.1”
40 2 layers of: 3.3” 2 layers of: 3.5”

According to Hunter Panels, one of the leading manufacturers of rigid polyisocyanyurate insulation, the reason for this change is due to the new ASTM C1289-11A testing method. The easiest explanation is that the edge of every board of insulation has a facer to it, which doesn’t have any “R” value to it. That size of the edge facer remains the same, whether it is 1 inch or 1.5 inches of insulation, so the thicker the insulation, the greater “R” value per inch. For more information on the actual testing method, check out Hunter Panels LTTR change page. The manufacturing methods of rigid polyisocyanurate insulation haven’t changed at all, so a piece of 1” rigid insulation manufactured in January 2013 will be identical to a piece manufactured in January 2014. All that has changed are the testing methods and the corresponding “R” values. Prior to 2014, to achieve an “R” value of 20, the commonly accepted minimum rigid insulation required in a roof removal and reinstall application was 3.3” thick. After January 1st, 2014, for an identical piece of insulation manufactured the exact same way, it will need to be 3.5” thick to achieve the same “R” value. However, if two staggered sheets of insulation are used, the “R” values change even more, since each individual sheet of rigid insulation loses the “R” value from that edge facer. So, to achieve an “R” value of 20 using two staggered rigid insulation sheets, you now need two layers of 1.8” insulation (Total thickness of 3.6”) instead of the previous two layers of 1.7” insulation (Total thickness of 3.4”, which is actually an “R” value of 20.4) For more information, Hunter Panels has an excellent FAQ’s section about R values on their website.

Why Choose Chaffee?

Our family business was founded in 1908, over 100 years ago. That’s quite an accomplishment, considering the average contractor stays in business for only 2 years. Since we were founded in 1908, four generations of Chaffee have owned the company, and four generations have worked at Chaffee, providing excellent commercial and industrial roofing services.

Chaffee Roofing Commercial Roof Services

Get a Free Consultation Today!

Whether you have a question about the types of commercial and industrial roofs and the roofing process or want to discuss your needs further, please fill out this brief form below, and someone will be in touch with you within 24 hours. If you need immediate assistance, our Emergency Phone is 401-432-7670.