New 2014 Polyisocyanurate “R” Values

Chaffee Roofing Commercial Roof Insulation
Discover changes in LTTR values for polyisocyanurate insulation from 2014, including varying "R" values per inch and impacts on insulation thickness requirements.

On January 1st, 2014, the Long-Term Thermal Resistance values (LTTR ) or “R” value for polyisocyanurate insulation will be reduced from 6 per inch to 5.6 per inch. To make things more confusing, the “R” value per inch is not consistent. The thicker the insulation, the greater the “R” value per inch. So, 1” polyisocyanurate insulation will have an “R” value of 5.6, where an identical 1.5” sheet will have an “R” value of 5.7 per inch. The following is a table comparing the old “R” values to the new “R” values:

One layer of rigid insulation

Thickness

Prior to 2014 “R” ValuesAfter 2014 “R” Values
LTTR Value“R” per inchLTTR Value“R” per inch
1”6.06.05.65.7
1.5”9.06.08.65.7
2”12.16.111.45.8
3”18.56.217.45.8
4”25.06.223.65.9

Two Layers of rigid insulation

“R” ValuePrior to 2014 ThicknessAfter 2014 Thickness
152 layers of: 1.3”2 layers of: 1.4”
202 layers of: 1.7”2 layers of: 1.8”
252 layers of: 2.1”2 layers of: 2.2”
302 layers of: 2.5”2 layers of: 2.6”
352 layers of: 2.9”2 layers of: 3.1”
402 layers of: 3.3”2 layers of: 3.5”

According to Hunter Panels, one of the leading manufacturers of rigid polyisocyanyurate insulation, the reason for this change is due to the new ASTM C1289-11A testing method. The easiest explanation is that the edge of every board of insulation has a facer to it, which doesn’t have any “R” value to it. That size of the edge facer remains the same, whether it is 1 inch or 1.5 inches of insulation, so the thicker the insulation, the greater “R” value per inch. The manufacturing methods of rigid polyisocyanurate insulation haven’t changed at all, so a piece of 1” rigid insulation manufactured in January 2013 will be identical to a piece manufactured in January 2014. All that has changed are the testing methods and the corresponding “R” values. Prior to 2014, to achieve an “R” value of 20, the commonly accepted minimum rigid insulation required in a roof removal and reinstall application was 3.3” thick. After January 1st, 2014, for an identical piece of insulation manufactured the exact same way, it will need to be 3.5” thick to achieve the same “R” value. However, if two staggered sheets of insulation are used, the “R” values change even more, since each individual sheet of rigid insulation loses the “R” value from that edge facer. So, to achieve an “R” value of 20 using two staggered rigid insulation sheets, you now need two layers of 1.8” insulation (Total thickness of 3.6”) instead of the previous two layers of 1.7” insulation (Total thickness of 3.4”, which is actually an “R” value of 20.4).

 

Share the Post:

Get In Touch Today

Fill out the form below and we will be sure to get back to you!

Address

Related Posts

14 Sep 2026
Learn how PVC plasticizer migration leads to roof cracking, shrinking, and failure. Discover its causes, long-term effects, and expert solutions to protect your roof.
9 Sep 2026
Unlock the benefits of R-30 roofing insulation. Learn how 5.2" polyisocyanurate boosts energy efficiency, meets codes, and enhances commercial roof performance.
27 Aug 2026
Heat welding TPO/PVC membranes creates leak-proof seams in commercial roofing. Find tools, steps, & tips for strong, lasting roof systems.